Description
Installed downstream of the main circuit-breaker, it compares the actual power consumption of the system to a preset maximum permitted value, and prevents tripping of the main circuit-breaker by switching off one non-prioritary load when the present threshold is exceeded. New original ABB part, traceable to the manufacturer. Availability and price on request.
Technical Specifications
| Input Current | 32 A |
|---|---|
| Input Voltage (Uin) | 230 (-15%/+10%) V AC |
| Rated Frequency (f) | 50/60 Hz |
| Power Consumption (@Pcons) | 6 V·A |
| Number of Contacts CO | 0 |
| Number of Contacts NC | 0 |
| Number of Contacts NO | 1 |
| Degree of Protection | Terminals IP20 ; Front IP51 |
| Ambient Air Temperature | Operation -10…45 °C ; Storage -10…65 °C |
| Mounting Type | DIN-Rail |
| Width in Number of Modular Spacings | 2 |
| Product Net Width | 36 mm |
| Product Net Height | 87.5 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Weight | 135 g |
| Built-In Depth (t2) | 65 mm |
| EAN | 8012542299011 |
| Catalog Description | Load management relay LCR |
| Delay Time (τ) | Load Disconnection 0…9999 s ; Between Connections 0…9999 s |
| Connecting Capacity | Rigid max. 4 mm² ; Flexible max. 6 mm² |
| Operating Humidity (RHamb) | Maximum, No Condensation 90 % |
| Screen Size | 1.408 in |
| Object Classification Code | K |
| Country of origin | Italy |
| Customs tariff number | 85364900 |
| Manufacturer standard delivery time | 8 days |
| Packaging unit | Box x 1 |
| Product status (supplier data) | Active |
Independent distributor — not an authorised ABB dealer. All technical parameters are taken verbatim from the official ABB product data for this exact order code; packaging, customs and delivery data come from the supplier list entry for the same code.