Description
The RCD block DDA200 series is suitable for assembly with MCBs S200 series and S300P. It assures protection against the effects of sinusoidal alternating and direct pulsating earth fault currents, protection, against indirects contacts and additional protection against direct (with sensitivity = 30 mA) contacts. Applications: residential, commercial, industrial. New original ABB part, traceable to the manufacturer. Availability and price on request.
Technical Specifications
| Number of Poles | 2P |
|---|---|
| Rated Current | 63 A |
| Rated Residual Current | 100 mA |
| Type of Residual Current | Type A |
| Leakage Current Type | A |
| Rated Voltage | 230/400 V |
| Rated Operational Voltage | 230 V |
| Rated Insulation Voltage | acc. to IEC/EN 60664-1 500 V |
| Rated Impulse Withstand Voltage | 4 kV |
| Rated Frequency | 50 / 60 Hz |
| Short-Circuit Current Rating (SCCR) UL/CSA | 1 kA |
| Test Voltage (Ut) | 195…254 V |
| Rated Current Sensitivity | 100 mA |
| Operating Characteristic | Instantaneous |
| Power Loss | Total 5 W |
| Power Supply Connection | Arbitrary |
| Depth | 69 mm |
| Height | 93 mm |
| Width | 70 mm |
| Weight | 395 g |
| EAN | 8012542795902 |
| Electrical Endurance | 10000 cycle |
| Number of Modules | 4 |
| Modular Spacings per DIN Rail | 4 |
| Tightening Torque | 2.8 N·m |
| Cable Cross-Section | Flexible Cable 0…25 mm²; Rigid Cable 0…25 mm² |
| Country of origin | Italy |
| Customs tariff number | 85362010 |
| Manufacturer standard delivery time | 24 days |
| Packaging unit | Box x 1 |
| Product status (supplier data) | Active |
Independent distributor — not an authorised ABB dealer. All technical parameters are taken verbatim from the official ABB product data for this exact order code; packaging, customs and delivery data come from the supplier list entry for the same code.