Description
The DS301C series is a 1P+N RCBO in one module width for the protection of end user single-phase circuits against overload and short-circuit currents, protection against the effects of sinusoidal alternating and direct pulsating earth fault currents, protection against indirect contacts and additional protection against direct contacts. DSX301C is part of the FlexLine portfolio. New original ABB part, traceable to the manufacturer. Availability and price on request.
Technical Specifications
| Type of Residual Current | Type A |
|---|---|
| Test Voltage (Ut) | 170 … 264 V |
| Dielectric Test Voltage | 2.5 kV |
| Rated Residual Breaking Capacity (IΔm) | EN 61009-1 6000 A | IEC 61009-1 4500 A |
| Power Supply Connection | Bottom |
| Contact Position Indication | Red ON / Green OFF |
| Number of Protected Poles | 1 |
| Number of Poles | 1P+N |
| Operating Characteristic | Instantaneous |
| Wire Stripping Length | 12 mm |
| Tripping Characteristic | B |
| Rated Operational Voltage | acc. to IEC 60898-1 230 V |
| Rated Insulation Voltage (U<sub>i</sub>) | acc. to IEC/EN 60664-1 500 V |
| Rated Impulse Withstand Voltage (U<sub>imp</sub>) | 4 kV |
| Input Voltage Type | AC |
| Rated Current (I<sub>n</sub>) | 16 A |
| Rated Residual Current | 30 mA |
| Rated Short-Circuit Capacity | 6 kA |
| Rated Frequency (f) | 50 Hz |
| Power Loss | Average per Pole 1.415 W | Phase Pole 2.11 W | Neutral Pole 0.72 W | Total 2.83 W |
| Overvoltage Category | III |
| Degree of Protection | IP2X | IP40 |
| Pollution Degree | 2 |
| Material Resource Reduction (wt. %) | Design for Reduced Resource Consumption – 45 % |
| Sustainable Material Content in Packaging (wt. %) | Recycled Cardboard – 71.18 % | Recycled Paper – 0 % |
| Position of Neutral Terminals | Right |
| Housing Type | Insulation group I – II, RAL 7035 |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Actuator Material | Insulation Group II, Black, Sealable |
| Terminal Type | Screw Terminals | Push-in Spring Terminals |
| Actuator Type | Toggle |
| Ambient Air Temperature | Operation -25 … 55 °C |
| Reference Ambient Air Temperature | 30 °C |
| Mounting Type | DIN-Rail |
| Mounting Position | Any |
| Standards | IEC/EN 61009-1 | IEC/EN 61009-2-1 |
| Width in Number of Modular Spacings | 1 |
| Product Net Width | 17.6 mm |
| Product Net Height | 85 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Weight | 110 g |
| Built-In Depth (<em>t<sub>2</sub></em>) | 69 mm |
| EAN | 8012542418658 |
| Catalog Description | Residual Current Circuit Breaker with Overcurrent Protection DSX301C – 1P+N – 30 mA – 16 A – B – Type A – Instantaneous |
| Carbon Footprint | Full Lifecycle 14 kg CO₂ eq |
| Offered with Takeback Services | Take Back for Recycling |
| Energy Limiting Class | 3 |
| Electrical Endurance | 7000 cycle |
| Mechanical Endurance | 7000 cycle |
| Number of Modular Spacings per DIN Rail | 1 |
| Fault Indication | Blue Flag Below Toggle |
| Tightening Torque | 1.2 N·m |
| Actuator Marking | I / O |
| Options Provided | Screwless |
| Accessories Available | No |
| Number of Modules | 1 |
| Environmental Conditions | 28 cycle | |with 25 °C / 95-100 % | |with 55 °C / 90-96 % |
| Unspsc | 39121601 |
| Object Classification Code | F |
| Etim9 | EC000905 – Earth leakage circuit breaker |
| Etim10 | EC000905 – Earth leakage circuit breaker |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops – Standard EN45555 – 78.41 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill | UL 2799 Zero Waste To Landfill Validation available |
| Extended Product Lifetime | Product Durability is Enhanced |
| Country of origin | Italy |
| Customs tariff number | 85363010 |
| Manufacturer standard delivery time | 5 days |
| Packaging unit | Package x 1 |
| Product status (supplier data) | Active |
Independent distributor — not an authorised ABB dealer. All technical parameters are taken verbatim from the official ABB product data for this exact order code; packaging, customs and delivery data come from the supplier list entry for the same code.